The water pump control system of fan

Used in the control system for the fire control, the pollution discharge and the domestic pump
[model meaning]


 


[Product brief introduction]
  the KWK series control cabinet, which has the protection functions for under pressure, overflow and so on and the function of manual, self-action, rotation of accidents, showing the running states and the feedback of information, is widely applied in the control system for kinds of water pump and fan in the industry and mining, the enterprise, the public building and so on. The system also may carry the special design and production through the user's actual situation to completely satisfy each kind of request for the users.

Ordinary control cabinet
[Control type and lectotype plan]
A. The control of liquid level (expressed with L): When the control of liquid level is running automatically, the start and stop of the water pump are controlled by the set-up on-off liquid level (common ball float establishment). The control of liquid level is generally used in situation of water supply to the basin or water tank.
B. The pressure control (expressed with P): When the pressure control is running automatically, the start and stop of the water pump are controlled by the set-up pressure (common electric contact manometer establishment). The pressure control is generally used in situation of water supply to the pipe network directly, for example, the water supply for life and kinds of constant voltage control system.
C. The temperature control (expressed with T): When the temperature control is running automatically, the start and stop of the water pump are controlled by the set-up temperature (common temperature control device establishment). The control is generally used in boiler system.
D. The time control (expressed with S): When the time control is running automatically, the start and stop of the water pump are controlled by the set-up time (common time control device establishment). The control is generally used in the situation of regular water supply, such as the school and business building.
E. The control of air condition (expressed with C): When the control of air condition is running automatically, the start and stop of the water pump are controlled by the linked signal of the air condition system.
F. The fire special-purpose control (expressed with X): When the fire special-purpose control is running automatically, the start and stop of the water pump are controlled by the fire alarm of the fire control system.
G. The sewage pump control (expressed with W): When the sewage pump control is running automatically, the start and stop of the water pump are controlled by the set-up liquid level of polluted water (common ball float establishment)
H. The manual control (expressed with M): When the manual control is not running automatically, the start and stop of the water pump are controlled by the manual on-off button.
  From the analysis above, we should choose the control mode based on the suitable automatic running situation and functions of the water pump.
[switching mode and lectotype plan of main pump and stand-by pump]
A. The manual switchover (expressed with H): The choice between the main pump and the stand-by pump depends on the switchover button on the control panel. The manual switchover is generally used in the situation of few times of water pump starting and little time of running, for example: situations of fire control, pollution discharge and so on.
B. Fixed automatic switchover (expressed with AS): The choice between the main pump and the stand-by pump switches automatically depending on the fixed time.
That is to say if the fixed switching time is 8 hours, the 1# pump runs for 8 hours and switches to another pump automatically, and the 2# pump switches again in the same way after 8 hours. The automatic switchover is generally used in the places of few times of water pump starting and long running time, such as the conditioning circulation.
C. The automatic alternating switchover (expressed with AC): The alternating switchover between the main pump and the stand-by pump is when activating signal comes, the 1# pump starts, and the 1# pump stops as soon as the activating signal disappears. But when the next activating signal comes, the 2# pump starts. It is generally used in the situation of frequent starting times and little running time, such as the constant voltage system.
  Synthesizing the analysis above, we choose switchover way of the main pump and the stand-by pump according to the on-off situation and the length of running time.
[The number and power of the control water pump]
  Choose the type according to the quantity and the power of water pump which are actually chosen by users.
[characteristics of starting way and lectotype plan]
A. The direct-on starting (direct-on starting when there is no indication): It is generally worked with the water pump below 15KW.
B. The starred and triangle reduced voltage starter (expressed with Y): When the water pump starts, the line is starred junction, and switches to the triangle running while the running finishes. It is generally worked with the 18.5KW-37KW water pump, and the initial firing current of is about 3.5 times larger than the nominal current.
C. the auto transfer reduced voltage starter (expressed with Z): When the water pump starts, it reduces the initial firing current, and the pump runs with total voltage after the starting finished. It is generally worked with 45KW-75KW water pump.
D. The soft start (expressed with R): when the water pump starts, it smoothly starts depending on the soft starter, and the pump runs with total voltage after the starting finished. It is generally worked with the water pump the power of is upper than 90KW.
  Synthesizing the analysis above, we choose starting way of the water pump according to the power range.
 