| The power distribution
system |
The power distribution system
DOMINO the DOMINO combined cubicle switchboard
[Brief Introduction] The DOMINO series
of combined cubicle switchboard are mainly used in the electric power
plant, each kind of factories and mines, the guesthouse and so on
as the power supply system with 50-60Hz AC, 380V fixed voltage or
660V below. And as the power distribution supply, the electric motor
control and the illumination power distribution, it may also be used
on the ships, the moving vehicles, the platform of marine petroleum,
and in the nuclear stations. |
| nominal working voltage |
380V、 360V |
| nominal insulating voltage |
660V |
| nominal working current |
horizontal bus |
225A-7800A |
| vertical bus |
225A-1600A |
| Nominal effective value of
short-time tolerant electric current (1 second/ peak value) |
horizontal bus |
30KA/120 KA |
| vertical bus |
30KA/120 KA |
| The cover protection rank |
IP20, IP 22 , IP 44, IP 54 |
| to the standard |
GB7251-87 IEC-439,ZBK36001-89 |
|
| [service
conditions]
The product should be used
in the buildings where the situation condition conforms to the following
1-4th section stipulation. The building should conform to the request
in GB53-83 ‘the Design Standard of 10KV and below Substation Capacity
in Industry and civil use’.
1st, the temperature of ambient mediator is not higher than +40℃,
not lower than - 5℃, and the average temperature is not higher than
+35℃ in 24 hours.
2nd, when the temperature is +40℃, the relative humidity should
not surpass 50%, when the temperature is +20℃, it should not surpass
90%.
3rd, the above sea level should not surpass 2000M.
4th, the product should be placed in a clean place without current-conducting
dust, corrosiveness medium, explosion hazard and fierce vibration.
5th, the product should be transported and stored in temperature
range of -25℃~+25℃, and should not surpass +70℃ in 24 hours. |
|
| The series of XJM7 low voltage electrical energy measuring meter
box
[Brief Introduction]
The KWP series
of illumination electrical energy measuring meter box is suitable
for the electrical energy central measuring management which is
used in the apartment building and the office building. It may install
the pulse electrical energy meter according to the needs of design,
to realize the computer management, and it leaves the position for
the installment of telemetering and the long range communication
equipment. In the meter box the small circuit breaker is installed,
which has the function of overload and short circuit protection.
The nominal current of electrical energy meter and circuit breaker
is selected by the design.
|
|
parameters
| nominal insulating voltage |
nominal working electricity |
nominal working current |
nominal frequency |
protection rank of cover |
| 660V |
380V、 200V |
special specification supplied for the bilateral agreement |
50Hz |
IP30 |
[working
conditions]
The meter box should be installed indoors,
and ought to be able for the normal use under the following condition:
1st, surrounding air temperature
Upper limit value is +45℃, while lower limit value is -5℃. The mean
value should not surpass +35℃ in 24 hours.
2nd, the atmospheric condition
The air is clean. When the maximum temperature is +45℃, its relative
humidity should not surpass 50%, but under the lower humidity, the
large relative humidity is permitted. For example when it is +20℃,
the relative humidity is 90%, but the possibility of accidental moderate
congealing dew should be considered because of the humidity change.
3rd, the sea level of the using place should not surpass 2000M. |
 |
[Brief Introduction]
he KWP series of low voltage electrical energy
measuring meter box is suitable for the measuring management of three-phase
four wire power and illumination. The merits are the large capacity,
the optional by-passing out switch according to the design and the
guards against electricity stealing. It is nimble, mobile, and reliable
equipment for power distribution measurement.
|
|